Combo cooling
For Telecom cabinets, shelters and enclosures.
With both Carbon Dioxide Emissions and Operating Costs getting increased attention in the Telecom industry, Dantherm was initially among the first to develop a solution to address both challenges. The solution is the new Combo Cooling product line combining Air Conditioning and Free Cooling to offer environmentally friendly climate control and generate optimum savings.
Dantherm Combo Cooling units are used for both in- and outdoor Telecom cabinets, shelters and electronics enclosures. The units are designed to save energy in normal running mode and have the advantage of back-up air conditioning during warm climates.
Ingress Protection Level 55
The Dantherm Combo Cooling system lives up to IP55 in the free cooling mode, protecting the cabinet, shelter or enclosure from the intrusion of dust and water. This makes the system perfect for even the most extreme environments and all geographical markets.
Dantherm Combo Cooling units have been running in the field since 1992.
-
Combo Cooling -
Combo Cooling
We look forward
to answering
your questions!
Online contact form
Facts:
Combo Cooling
Total heat management
Operational modes:
Free Cooling
Air Conditioning
Emergency cooling
Heating
Humidity Detection
| Dantherm Combo Cooling Capacities | 2000/135 |
|---|---|
| Voltage AC or DC | AC and DC |
| Voltage in VAC / VDC | 230 and 48 |
| Frequency in Hz | 50 / 60 |
| Free Cooling capacity in kW at Δt = 10°C | 1,35 |
| Free Cooling capacity in kW at Δt = 7°C | 0,95 |
| Free Cooling capacity in W/K | 135 |
| Air Conditioner capacity in kW at internal 35°C and ambient 35°C |
2,0 |
| Weight in kg | 68 |
Applications
- Radio base stations
- Telecom shelters
- Electronics enclosures
- Power supply rooms
- Network & computer rooms
- Drive stations
- Kiosks
- Automation control cabinets
Features and Benefits
Dantherm Combo Cooling
- Energy-efficient cooling system
- Total heat management with free cooling, active cooling and heating
- Easy installation in indoor and outdoor cabients and enclosures
- Ingress protection level 55 (IP55) against particles and water
- Emergency cooling mode in case of power outage
- Digital controller for full thermal management and
surveillance and changeable settings
China EN
Global
USA
Mexico
Denmark
Sweden
Norway
France
Germany
United Kingdom
Russia
